THE HONG KONG GOVERNMENT GAZETTE, AUGUST 3, 1934.
Lamp- holders.
Disused wiring and apparatus.
Diagram of wiring.
Fire appliances.
Installations
ed portions of premises.
93. All lampholders within normal reach shall be kept fitted with lamps.
94. Wiring and apparatus which will be out of use during the run of a production or which are not likely to be required for a period exceeding one month, shall be disconnected during such period by the withdrawal of the fuses on both poles Permanently disused wiring and apparatus shall be removed.
95. A diagram and/or schedule indicating clearly the arrangements of the circuits and sub-circuits, the position of the distribution boards and the sizes of the cables shall be kept in an accessible position on the premises.
96. At least one bucket filled with dry sand, or а chemical extinguisher of a type approved by the Chief Officer of the Fire Brigade for the purpose, shall be provided and kept readily accessible in the following positions viz, intake rooms, main distribution rooms, motor generator rooms, near stage switch boards and in such other positions as the Chief Officer of the Fire Brigade may consider necessary.
97. In cases in which the premises form part of larger for unlicens premises, the electrical services for such part shall not be used for any purpose in connection with the remaining parts of the premises, except with the consent in writing of the Licensing Authority and in accordance with any conditions of such consent.
Radio
98. Radio apparatus or any electrical amplifying installations. apparatus shall not be installed or used, except with the con- sent in writing of the Licensing Authority and in accordance with
any conditions of such consent.
Gas meters and main control.
Guards for burners.
Separation of supplies.
Piping.
Gas installations.
99. Gas meters and the connections thereto shall be installed in an enclosure constructed of fire-resisting materials. The enclosure shall be ventilated to the open air and shall be reserved exclusively for the meters and connections. A main cock with fixed handle shall be provided and shall be accessible only to authorised persons.
100. Gas burners shall be guarded by wire guards or glass globes or other efficient means and shall be protected against draughts to the satisfaction of the Licensing Authority. In open exitways or other exposed positions the gas burners shall be enclosed in weatherproof lanterns. Fittings and ac- cessories liable to interference or damage shall be protected to the satisfaction of the Licensing Authority.
101. Any connection to the gas mains for the supply of one of the systems of lighting required by regulation 61 shall be made in such a manner that an accident to any other gas services or supplies cannot jeopardise the minimum lighting. A separate connection to the gas main shall be made for the supply to any large boiler, engine or cooking plant and to such other apparatus as the Licensing Authority may determine.
102.-(1) Piping other than the connections to the meter shall be of hard metal and shall be securely fixed away from electrical wiring and apparatus. Where liable to corrosion, piping shall be efficiently protected by painting or such other method as may be approved by the Licensing Authority.