Loading and unloading of tank wagons,
Repairs to tanks on
tank wagons.
Vehicles not to be fuelled
directly fromNY, tank wagons.
Tank wagens to be altended.
Fire, etc.
150
119. When any tank wagon is being loaded or unloaded-
(a)
if the tank wagon is mechanically propelled, the engine shall not be started until all tanks are securely closed unless the wagon is fitted with an exhaust flame trap; and
(b) adequate provision shall be made to prevent the accumulation
of static electricity.
120. No person shall repair, or cause or permit to be repaired, ou any tank wagon any tank or self contained compartment involving the use of artificial heat, unless the tank and the compartment has been certified free from inflammable vapour by an approved person.
121. No person shall fuel any vehicle directly from any tank wagon.
122. No person shall convey, or cause or permit to be conveyed. on any tank wagon any dangerous goods of category 5. class 1 or 2. in liquid form unless the wagon is attended by at least one person, in addition to the driver, having reasonable experience in the carriage of such liquids in bulk.
123. No person shall carry, or cause or permit to be carried, any not permitted fire, matches or other means of ignition, or any artificial lighting capable of igniting inflammable vapour, on any tank wagon containing any dangerous goods of category 5, class 1 or 2, in liquid form.
on vehicles
conveying
dangerous
goods of category 3. class 1 or 2
Application for licence to More.
Bulk storage and dispensing facilities.
124. (1) Every application, pursuant to any of the provisions of section 5 of the Ordinance, for any licence to store ia bulk any dangerous goods in liquid form shall be made in writing addressed to the Authority and shall be accompanied by two copies of a plan, as nearly as may be to scale, of the place or the area to be occupied by the installation including, if applicable, accommodation for offices or other administrative purposes required in respect of such storage, and every such plan shall include, so far as may be applicable, the following particulars-
(a) the siting of every tank, pipeline or other plant or structure to
be erected at such place or within such area;
151
(d) the capacity of every such tank;
(e) the plan of any bunding walls or protective fencing:
( the plan of any drainage system:
(g) such other particulars, if any, as the Authority may require to
be shown on the plan.
(2) Every plan submitted pursuant to the provisions of paragraph (1) shall be accompanied by-
(a) a statement in writing declaring the type or types of liquid to
be stored; and
(b) two copies of the design and specifications to which it is
intended that-
(i) any jankage.
(ii) any ancillary container,
(iii) any pipeline or other plant.
(iv) any filling, dispensing or pumping equipment.
is to be constructed.
(3) Every plan and every set of designs and specifications, or any modification thereof. which is approved by the Authority shall be endorsed to that effect and one copy shall be returned to the applicant and one copy retained by the Authority.
125. No licence for the storage of any dangerous goods in liquid Conditions form shall be granted or renewed by the Authority unless he is satisfied for grant of in relation to the installation required that---
(a) the site of the installation and the plan referred to in regulation 124 have been approved by him and the construction of the installation conforms with the plant
(8) any-
(i) tankage,
(b) the plan of every such tank, pipeline or other plant or
structure and the use to which it will be put;
1
(c) the distance between any such tank. pipeline, plant or structure and any other tank, pipeline, plant or structure or any domestic or other premises or any public place;
(ii) ancillary container,
(ii) pipeline or other plant.
(iv) filling, dispensing or pumping equipment.
is constructed according to the designs and specifications there- for approved together with such plan;
(c) all electrical equipment is securely insulated and, where necessary, earthed and otherwise installed and fitted to his satisfaction:
(d) the installation is free from traps likely to accumulate inflam-
mable liquid or vapour:
Hoenoca to
store in bruth.