Places of Public Entertainment Regulations
[CAP. 172
B 29
[Subsidiary]
(2) If considered necessary by the licensing authority for obviating risk of shock, guardrails shall be constructed of English oak or teak, and any metal within reach of a person on the platform shall be satisfactorily protected.
79. (1) Wiring shall not be run in a ventilating duct, flue or air shaft, or installed in a lift unless it is essential for the operation of the lift.
(2) A cable duct shall be stopped at any point at which it passes through a fire-resisting wall or floor so as to prevent the passage of fire or smoke from one section of the duct to another.
(3) Cable ways shall not be formed in the protective covering of structural steel work.
(4) Conduits shall be efficiently protected against corrosion.
(5) Where cables are permitted without conduits or similar protection (e.g. for connexions to battens), they shall be efficiently protected by an asbestic or other non-inflammable covering and shall be supported to the satisfaction of the licensing authority. This paragraph shall not apply to cables used in connexion with portable apparatus.
(6) The use of flexible cord or cable shall be avoided whenever practicable. In any case in which such a conductor is permitted it shall be as short as possible. Each cord or cable shall be fitted with a separate plug connexion.
(7) Sub-circuits for current-consuming devices other than lamps shall not be connected to lighting circuits:
Provided that any such device which consumes not more than 500 watts may be connected to a separate sub-circuit of a lighting distribution board.
(8) Sub-circuits from one source of supply only shall be taken into any fitting, and a voltage greater than 250 shall not exist between any conductors in any fitting.
(9) Multiple core and bunch cables shall be suitably insulated and protected.
80. (1) All suspended fittings or apparatus, other than small single-lamp pendants fitted at a height of less than 3 m above the floor level, shall be provided with satisfactory means of suspension independent of the conductors. Heavy pendent fittings or apparatus shall, unless rigidly fixed, be provided with 2 means of suspension independent of the conductors. A self-sustaining winch shall be provided for such fittings or apparatus, if the licensing authority so requires. Proper means of access shall be provided for the inspection and maintenance of the fittings or apparatus.
Wiring.
Fittings, accessories, etc. L.N. 63/77.