1985 Ed.]

Building (Construction) Regulations

[CAP. 123

B 127

[Subsidiary]

TABLE C

STEEL COLUMNS AND BEAMS

Minimum thickness of protection in mm for

period of

2 3 4 5

Construction and Materials hours hours hour hour

SOLID PROTECTION

Columns

Concrete not inferior to that designated Grade III in regulation 19 and reinforced

*The thickness of protection on any projecting cleat, projecting rivet head and the like need not exceed 25 mm.

Solid bricks of burnt clay or sand lime

65* 50* 25 25

75 50 50 50

Solid blocks: reinforced in every horizontal joint

(i) Foamed slag or pumice concrete/ (ii) Gypsum blocks

65 50 $3 50

50 50 皆皆 50

50 50 88 50

Sprayed Asbestos...

50 45. 7.

Beams

Concrete not inferior to that designated Grade III in regulation 19 and reinforced

65* 50* 25 25

*The thickness of protection on the upper surface of the upper flange of an internal beam, and on any projecting cleat, projecting rivet head and the like need not exceed 25 mm.

Sprayed Asbestos ............

-50 15

HOLLOW PROTECTION

Columns

Solid bricks of burnt clay or sand lime: reinforced in every horizontal joint

115 75 50 50

Solid bricks of foamed slag or pumice concrete or gypsum: reinforced in every horizontal joint

75 50 50 50

Moulded asbestos bound in position with nicrome wire not less than 1.6 mm diameter, the wires to be sunk in grooves not less than 3 mm deep in the outer surface of the asbestos and the grooves and all joints in the asbestos to be filled with refractory cement

Cement plaster or cement-lime plaster on metal lathing

65 40 125 25

19

Cement plaster or cement-lime plaster on metal lathing with reinforcement over rendering coat ..

25

Gypsum plaster on metal lathing

22 16

Gypsum plaster on 9.5 mm gypsum plaster board with 1.6 mm diameter wire binding at 100 mm pitch

12.5