CAP. 123 Building (Construction) Regulations

[1985 Ed.

{Subsidiary]

L.N. 294/76.

THIRD SCHEDULE

[reg. 182.]

MINIMUM REQUIREMENTS FOR CONSTRUCTION AND MATERIALS TO BE CAPABLE OF RESISTING THE ACTION OF FIRE FOR SPECIFIED PERIODS

TABLE A

WALLS AND PARTITIONS

Minimum thickness in mm (excluding plaster) for period of

Construction and Materials

3 hours 4 hours 1 hour 4 hours 2 hours 1 hour

SOLID CONSTRUCTION--

Bricks of clay, concrete or sand lime

No plaster

*Where plastered at least 12.5 mm thick on each side and where the wall does not exceed 3 m in either height or length, the thickness for this period may be 100 mm.

225 225* 100 100

Concrete blocks

Class 1 Aggregate

No plaster.

100

Plastered at least 12.5 mm thick on each side

100

Class 2 Aggregate

No plaster

100

Plastered at least 12.5 mm thick on each side

100

Gypsum blocks

No plaster

100

Plastered at least 12.5 mm thick on each side

75 75 65 50 75 75 75 50

Wood wool slabs Plastered at least 12.5 mm thick on each side

75 50 50

Reinforced concrete

Plaster board

HOLLOW BLOCK CONSTRUCTIONS- Clay blocks

Aggregate in accordance with regulation 18(2), with minimum concrete cover to reinforcement of 25 mm

Supported at top and bottom edges in steel channels and plastered on each side at least 15 mm thickness with gypsum plaster

Plastered at least 12.5 mm thick on each side and shells not less than 20 mm thick:-

175 100 75 75

1 cell in each block and each block not less than 50 per cent solid

100 75

1 cell in each block and each block not less than 30 per cent solid

150

2 cells in each block and each block not less than 50 per cent solid

225 100

2 cells in each block and each block not less than 30 per cent solid

150