NOV 10 (87 11:52 TIBCOOL HK GOVI

1987-11-04

18:12

GNPJVC SHENZHEN

65709

UNPJVC

15

日期

memorandum

date

发過

我方发文物好

Executive Committee

to

our ref.

我们

General Manager

from

購目

subject

蚪方黻文编号 your rel.

P.3

P.02

3rd November, 1987

白素 dated

Implementation of Technical Solution for Non-conformance

of Omitted Starter Rebars in First Layer of Unit 1 Raft

1.

2.

The purpose of this report is to present to the Directors the the progress of the treatment of the above non-conformance, and conditions based on which consideration is being given to release the hold point on pouring of concrete in the second layer of the reinforced concrete foundation raft for the Unit 1 reactor building at Days Bay,

Background

The

The first layer of Unit 1 Raft was completed on 11.9.1987. non-conformance of omitted starter rebars in the first layer of Unit 1 Raft was discovered on 14.9. and 15.9.1987 by GNPJVC and the contractor, HCCM. HCCM then stopped further reinforcement work.

The omission referred to 316 out of a total of 376 inclined starter It was caused by rebare in the first layer of the Unit 1 Raft. misinterpretation of the construction drawings by the contractor. The event was reported to the Chinese Authorities on 21.9.1987, the Executive Committee on 24.9.1987, and to the Board and shareholders on 29.9.1987.

The JVC's policy on the issue was then as follows:

(a) To put a hold point from the pouring of concrete on Unit 1

reactor building raft.

(b)

(c)

To check that all other types of reinforcing bars in the first layer had been placed correctly.

To arrange a complete review by the designer, EdF, and in line with the policy of giving priority to safety and quality, determine technical solution which completely meets all requirements of the original design.

BH DATE

22 TO

...../2

# REMARKS

Share This Page