1984 Ed.] Building (Refuse Storage Chambers and Chutes) Regulations

[CAP. 123

H 7

(4) Every hopper and frame shall be constructed of galvanized or stainless mild steel plate, of not less than 3 mm thickness, or other approved material.

(5) The inner plate of every hopper shall project downward at an angle of not less than 45° to the horizontal when the hopper is closed.

24. The recess into which any hopper is fitted shall be of a size adequate to house the frame and the moving parts of the hopper so that no part of the frame or hopper projects into the refuse chute.

25. The junction of every hopper with the refuse chute shall be so made as to provide a continuous smooth and impervious surface.

SCHEDULE

[Subsidiary]

Hopper recess.

Junction of hopper with refuse chute.

[reg. 3.]

Description of building Total floor area as shown on plan Description of storage chamber Minimum floor space of storage chamber Domestic Building Non-domestic Building (a) Usable floor space 1,320 m2 or more but less than 13,200 m2 (b) Usable floor space 13,200 m2 or more Composite Building (a) Aggregate usable floor space 1,320 m2 or more but less than 13,200 m2 (b) Aggregate usable floor space 13,200 m2 or more Storage chamber Total usable floor space in m2 divided by 440 Storage chamber with vehicular access Total usable floor space in m2 divided by 440 (a) Usable floor space 3,960 m2 or more but less than 39,600 m2 Storage chamber Total usable floor space in m2 divided by 1,320 (b) Usable floor space 39,600 m2 or more Storage chamber with vehicular access Total usable floor space in m2 divided by 1,320 Storage chamber Aggregate of:
(a) the total usable floor space of the domestic building component in m2 divided by 440; and
(b) the total usable floor space of the non-domestic building component in m2 divided by 1,320 Storage chamber with vehicular access Aggregate of:
(a) the total usable floor space of the domestic building component in m2 divided by 440; and
(b) the total usable floor space of the non-domestic building component in m2 divided by 1,320

Edit History

2026-05-04 08:38:03 · NVIDIA / meta/llama-4-maverick-17b-128e-instruct
Live
View comparison
AI Proofread
1984 Ed.] Building (Refuse Storage Chambers and Chutes) Regulations [CAP. 123 H 7 (4) Every hopper and frame shall be constructed of galvanized or stainless mild steel plate, of not less than 3 mm thickness, or other approved material. (5) The inner plate of every hopper shall project downward at an angle of not less than 45° to the horizontal when the hopper is closed. 24. The recess into which any hopper is fitted shall be of a size adequate to house the frame and the moving parts of the hopper so that no part of the frame or hopper projects into the refuse chute. 25. The junction of every hopper with the refuse chute shall be so made as to provide a continuous smooth and impervious surface. SCHEDULE [Subsidiary] Hopper recess. Junction of hopper with refuse chute. [reg. 3.] Description of building Total floor area as shown on plan Description of storage chamber Minimum floor space of storage chamber Domestic Building Non-domestic Building (a) Usable floor space 1,320 m2 or more but less than 13,200 m2 (b) Usable floor space 13,200 m2 or more Composite Building (a) Aggregate usable floor space 1,320 m2 or more but less than 13,200 m2 (b) Aggregate usable floor space 13,200 m2 or more Storage chamber Total usable floor space in m2 divided by 440 Storage chamber with vehicular access Total usable floor space in m2 divided by 440 (a) Usable floor space 3,960 m2 or more but less than 39,600 m2 Storage chamber Total usable floor space in m2 divided by 1,320 (b) Usable floor space 39,600 m2 or more Storage chamber with vehicular access Total usable floor space in m2 divided by 1,320 Storage chamber Aggregate of:(a) the total usable floor space of the domestic building component in m2 divided by 440; and(b) the total usable floor space of the non-domestic building component in m2 divided by 1,320 Storage chamber with vehicular access Aggregate of:(a) the total usable floor space of the domestic building component in m2 divided by 440; and(b) the total usable floor space of the non-domestic building component in m2 divided by 1,320
Baseline (Original)
1984 Ed.] Building ( Refuse Storage Chambers and Chutes) Regulations [CAP. 123 H 7 (4) Every hopper and frame shall be constructed of galvanized or stainless mild steel plate, of not less than 3 mm thickness, or other approved material. (5) The inner plate of every hopper shall project downward at an angle of not less than 45 to the horizontal when the hopper is closed. 24. The recess into which any hopper is fitted shall be of a size adequate to house the frame and the moving parts of the hopper so that no part of the frame or hopper projects into the refuse chute. 25. The junction of every hopper with the refuse chute shall be so made as to provide a continuous smooth and impervious surface. SCHEDULE [Subsidiary] Hopper recess. Junction of hopper with refuse chute. [reg. 3.] Description of building Total floor area as shown on plan Description of storage chamber Minimum floor space of storage chamber Domestic Building (a) Non- domestic Building Usable floor space 1 320 m2 or more but less than 13. 200 m 2 (6) Usable floor space 13 200 m2 or more (a) Usable floor space 3 960 m2 or more but less than 39 600 m2 (b) Usable floor space 39 600 m2 or more Composite (a) Aggregate usable Building floor space 1 320 m2 or more but less than 13 200 m2 (b) Aggregate usable floor space 13 200 m2 or more Storage chamber Total usable floor space in m2 divided by 440 Storage chamber Total usable floor space in m2 divided by 440 with vehicular access Storage chamber Total usable floor space in m2 divided by 1 320 Storage chamber Total usable floor space in m2 divided by I 320 with vehicular access Storage chamber Aggregate of- Storage chamber with vehicular access (a) the total usable floor space of the domestic building component in m divided by 440; and (b) the total usable floor space of the non-domestic building component in m2 divided by 1 320 Aggregate of--- (a) the total usable floor space of the domestic building component in m divided by 440; and (b) the total usable floor space of the non-domestic building component in m2 divided by 1 320
2026-05-04 08:38:03 · Baseline
View content

1984 Ed.] Building ( Refuse Storage Chambers and

Chutes) Regulations

[CAP. 123

H 7

(4) Every hopper and frame shall be constructed of galvanized or stainless mild steel plate, of not less than 3 mm thickness, or other approved material.

(5) The inner plate of every hopper shall project downward at an angle of not less than 45 to the horizontal when the hopper is closed.

24. The recess into which any hopper is fitted shall be of a size adequate to house the frame and the moving parts of the hopper so that no part of the frame or hopper projects into the refuse chute.

25. The junction of every hopper with the refuse chute shall be so made as to provide a continuous smooth and impervious surface.

SCHEDULE

[Subsidiary]

Hopper recess.

Junction of hopper with refuse chute.

[reg. 3.]

Description of building

Total floor area as shown on plan

Description of storage chamber

Minimum floor space of storage chamber

Domestic Building

(a)

Non- domestic Building

Usable floor space 1 320 m2 or more but less than

13. 200 m 2

(6) Usable floor space 13 200 m2 or more

(a) Usable floor space

3 960 m2 or more

but less than

39 600 m2

(b) Usable floor space 39 600 m2 or more

Composite (a) Aggregate usable

Building

floor space

1 320 m2 or more

but less than

13 200 m2

(b) Aggregate usable

floor space

13 200 m2 or more

Storage chamber Total usable floor space

in m2 divided by 440

Storage chamber

Total usable floor space in m2 divided by 440

with vehicular access

Storage chamber Total usable floor space

in m2 divided by 1 320

Storage chamber

Total usable floor space in m2 divided by I 320

with vehicular

access

Storage chamber Aggregate of-

Storage chamber with vehicular

access

(a) the total usable

floor space of the domestic building component in m divided by 440; and

(b) the total usable

floor space of the non-domestic building component in m2 divided by 1 320

Aggregate of--- (a) the total usable

floor space of the domestic building component in m divided by 440; and

(b) the total usable

floor space of the non-domestic building component in m2 divided by 1 320

Comments