Building (Construction) Regulations

[CAP. 123

B 97

147. Flat slab panels shall be assumed to be divided into--

(a) a middle strip which shall run the full length of the panel symmetrical about the centre line of the panel and the width of the panel;

(b) a column strip which shall run the full length of the panel and consist of 2 adjacent quarter panel widths, 1 on each side of the column centre line,

as shown in Diagram 5.

5

DIAGRAM 5

Division of flat slab panels into column and middle strips

[Subsidiary]

Division of

panels in flat slab construction.

0.5 D

1

MID-SPAN AND

POSITION OF MAXIMUM POSITIVE

MOMENT

POSITION OF MAXIMUM

NEGATIVE MOMENT

1

I

HALF

-COLUMN-

-MIDDLE | STRIP

STRIP

0.25 L2

0.25 L2 0.25 L2

HALF -COLUMN- STRIP

0.25 L2

than

148. The minimum thickness t, of a flat slab shall be not less

(a) 125 mm;

Minimum thickness of flat slabs.

L.N. 294/76.

(b)

L

32

for end panels without drops:

(c)

L

36

for fully continuous interior panels without drops and for end panels with drops;

(d)

L

40

for fully continuous interior panels with drops.

whichever is the greatest.

149. (1) The critical sections for shear shall be assumed to be-

(a) at a distance from the column head or, when no column head is provided, from the column of the thickness of the drop, or, where no drop is provided, the thickness of the slab; and

Shearing stresses in flat slabs.

Edit History

2026-05-04 08:21:45 · NVIDIA / meta/llama-4-maverick-17b-128e-instruct
Live
View comparison
AI Proofread
1985 Ed.] Building (Construction) Regulations [CAP. 123 B 97 147. Flat slab panels shall be assumed to be divided into-- (a) a middle strip which shall run the full length of the panel symmetrical about the centre line of the panel and the width of the panel; (b) a column strip which shall run the full length of the panel and consist of 2 adjacent quarter panel widths, 1 on each side of the column centre line, as shown in Diagram 5. 5 DIAGRAM 5 Division of flat slab panels into column and middle strips [Subsidiary] Division of panels in flat slab construction. 0.5 D 1 MID-SPAN AND POSITION OF MAXIMUM POSITIVE MOMENT POSITION OF MAXIMUM NEGATIVE MOMENT 1 I HALF -COLUMN- -MIDDLE | STRIP STRIP 0.25 L2 0.25 L2 0.25 L2 HALF -COLUMN- STRIP 0.25 L2 than 148. The minimum thickness t, of a flat slab shall be not less (a) 125 mm; Minimum thickness of flat slabs. L.N. 294/76. (b) L 32 for end panels without drops: (c) L 36 for fully continuous interior panels without drops and for end panels with drops; (d) L 40 for fully continuous interior panels with drops. whichever is the greatest. 149. (1) The critical sections for shear shall be assumed to be- (a) at a distance from the column head or, when no column head is provided, from the column of the thickness of the drop, or, where no drop is provided, the thickness of the slab; and Shearing stresses in flat slabs.
Baseline (Original)
1985 Ed.] Building (Construction) Regulations [CAP. 123 B 97 147. Flat slab panels shall be assumed to be divided into-- (a) a middle strip which shall run the full length of the panel symmetrical about the centre line of the panel and the width of the panel; (b) a column strip which shall run the full length of the panel and consist of 2 adjacent quarter panel widths, 1 on each side of the column centre line, as shown in Diagram 5. 5 DIAGRAM 5 Division of flat slab panels into column and middle strips [Subsidiary] Division of panels in flat slab construction. 0.5 D 1 MID-SPAN AND POSITION OF MAXIMUM POSITIVE MOMENT POSITION OF MAXIMUM NEGATIVE MOMENT 1 I HALF -COLUMŃ- -MIDDLE | STRIP STRIP 0-25 £2 ì 0-29 £2 0-25 L2 HALF -COLUMN- STRIP 0-25 £2 than 148. The minimum thickness 1, of a flat slab shall be not less (a) 125 mm; Minimum thickness of flat slabs. L.N. 294/76. (b) L 32 for end panels without drops: (c) L 36 for fully continuous interior panels without drops and for end panels with drops; L (d) for fully continuous interior panels with drops. 40 whichever is the greatest. 149. (1) The critical sections for shear shall be assumed to be- (a) at a distance from the column head or, when no column head is provided, from the column of the thickness of the drop, or, where no drop is provided, ¦ the thickness of the slab; and Shcaring stresses in flat slabs. !
2026-05-04 08:21:45 · Baseline
View content

1985 Ed.]

Building (Construction) Regulations

[CAP. 123

B 97

147. Flat slab panels shall be assumed to be divided into--

(a) a middle strip which shall run the full length of the panel symmetrical about the centre line of the panel and the width of the panel;

(b) a column strip which shall run the full length of the panel and consist of 2 adjacent quarter panel widths, 1 on each side of the column centre line,

as shown in Diagram 5.

5

DIAGRAM 5

Division of flat slab panels into column and middle strips

[Subsidiary]

Division of

panels in flat slab construction.

0.5 D

1

MID-SPAN AND

POSITION OF MAXIMUM POSITIVE

MOMENT

POSITION OF MAXIMUM

NEGATIVE MOMENT

1

I

HALF

-COLUMŃ-

-MIDDLE | STRIP

STRIP

0-25 £2

ì 0-29 £2 0-25 L2

HALF -COLUMN- STRIP

0-25 £2

than

148. The minimum thickness 1, of a flat slab shall be not less

(a) 125 mm;

Minimum thickness of flat slabs.

L.N. 294/76.

(b)

L

32

for end panels without drops:

(c)

L

36

for fully continuous interior panels without drops and for end panels with drops;

L

(d) for fully continuous interior panels with drops.

40

whichever is the greatest.

149. (1) The critical sections for shear shall be assumed to be-

(a) at a distance from the column head or, when no column head is provided, from the column of the thickness of the drop, or, where no drop is provided, ¦ the thickness of the slab; and

Shcaring stresses in flat slabs.

!

Comments