TABLE D
REINFORCED CONCRETE COLUMNS AND BEAMS
Construction and Materials
Minimum overall size of column in mm for period of 4 hours 3 hours 2 hours 1 hour Reinforced concrete columns 450 300 225 Reinforced concrete columns with light 50 mm mesh reinforcement in the concrete cover to longitudinal reinforcement 300 225 Reinforced concrete beams Where the minimum thickness of concrete cover to: main reinforcement specified in this Table exceeds that required by regulation 115 the excess cover may be provided by renderings of cement plaster, cement-lime plaster or gypsum plaster, on a mesh reinforcement fixed to the concrete of the beam. Minimum concrete cover to longitudinal reinforcement in columns in mm for period of 4 hours 2 hours 1 hour 65 50 25 25 Minimum concrete cover to main reinforcement in mm for period of 4 hours 2 hours 1 hour 65 50 25 15TABLE E
STAIRS
Construction and Materials
Minimum thickness in mm for period of 4 hours 2 hours 1 hour 1. Reinforced concrete construction- (i) minimum thickness at waist of slab 100 100 75 65 (ii) concrete cover to reinforcement 65 65 15 15 2. Structural timber construction (timber with all joints in treads, risers and flooring, tongued and grooved or cross tongued)— (i) Soffit unprotected Minimum finished solid thickness in any part... (ii) Soffit protected with (a) plaster not less than 16 mm in thickness on metal lathing, or (b) sheets of incombustible material not less than 5 mm in thickness on backing of close jointed boarding not less than 12 mm in thickness, or (c) sheets of incombustible material not less than 5 mm in thickness bedded to plaster and fixed securely to the carriages and joists, minimum finished solid thickness in any part... 45 301
1985 Ed.]
Building (Construction) Regulations
[CAP. 123
B 129
[Subsidiary]
TABLE D
REINFORGED CONCRETE COLUMNS AND BEAMS
}
Construction and Materials
Minimum overall size of column in mm for period of
?
3
4
$
4
2
!
Reinforced concrete columns
Reinforced concrete columns with light 50 mm mesh reinforcement in the concrete cover to longitudinal reinforcement
Reinforced concrete beams
Where the minimum thickness of goncrete cover to: main reinforcement specified in this Table exceeds that required by regulation 115 the excess cover may be provided by renderings of cement plaster, cement- lime plaster or gypsum plaster, on a mesh reinforce- ment fixed to the concrete of the beam.
hours hours hour; hour
450 300 225
300 225
Minimum concrete cover to longitudinal reinforcement in columns in mm for period of
41 2
1
hours hours hour hour
65 50 25 25
Minimum concrete cover to main reinforcement in mm for period of
4
2 1
+ hours hours hour hour
65
50 25 15
TABLE E
STAIRS
Construction and Materials
Minimum thickness in mm for period of
4
2 1 hours! hours hour hour
1.
Reinforced concrete construction-
(i) minimum thickness at waist of slab
100
(ii) concrete cover to reinforcement
25
100
75 65 65
15 15
15
2.
Structural timber construction (timber with all joints in treads, risers and flooring, tongued and grooved or cross tongued)—
(i) Soffit unprotected
Minimum finished solid thickness in any part...!
(ii) Soffit protected with
(a) plaster not less than 16 mm in thickness
on metal lathing, or
(b) sheets of incombustible material not less than 5 mm in thickness on backing of close jointed boarding not less than 12 mm in thickness, or
(c) sheets of incombustible material not less than 5 mm in thickness bedded to plaster and fixed securely to the carriages and joists, minimum finished solid thickness in any part ...
45
30
1