1950_ELECTRICITY_SUPPLY_REGULATIONS — Page 4

HK Historical Laws 香港歷史法例 All AI Reviewed

CAP. 103]

[R. 2 cont.]

Introduction of three-wire system into consumer's premises.

Minimum size of conductors.

Insulation test of low pressure and medium pressure mains.

Testing of insulation of all parts of high pressure circuit.

Electricity Supply.

(d) where the supply is for any special purpose other than those above mentioned, or where the pressure of the supply exceeds the limits of medium pressure, it shall be subject to such other regulations as the Governor in Council may prescribe.

3.

When the pressure between the outer conductors of a three-wire system exceeds 250 volts and the three wires of the system or two pairs of wires are brought into a consumer's premises, the supply shall be given to two pairs of terminals arranged in such a manner that there shall be no danger of any shock, and the wiring from those terminals shall be kept distinct.

4. The sectional area of the conductor in any electric line other than low tension laid or erected in any street after 2nd December, 1921, shall not be less than that of a strand of seven wires, each of which is of No. 22 standard wire gauge, and the sectional area of every wire in a strand forming any such conductor shall not be less than that gauge, and where such stranded conductor is erected it shall be suspended from a suitable bearer wire or shall be protected by a suitable cradle fixed underneath. In the case of low tension conductors in any electric line the sectional area shall not be less than that of a single wire of No. 16 standard wire gauge efficiently insulated.

This regulation shall not apply in the case of an electric line placed in a lamp post.

5. Every low pressure and medium pressure main, after having been placed in position and before it is used for the purposes of supply, shall withstand a pressure equal to the maximum pressure to which it is intended to be subjected in use, and in any case at least 200 volts, and further, before being used as aforesaid it shall be tested for insulation, and the company shall duly record the results of the tests of each main or section of a main.

6.

A high pressure circuit shall not be brought into use unless the insulation of every part thereof has withstood the continuous application, during one hour, in the case of every electric line, of a pressure equal to the full

180

Edit History

2026-05-03 20:34:43 · NVIDIA / meta/llama-4-maverick-17b-128e-instruct
Live
View comparison
AI Proofread
CAP. 103] [R. 2 cont.] Introduction of three-wire system into consumer's premises. Minimum size of conductors. Insulation test of low pressure and medium pressure mains. Testing of insulation of all parts of high pressure circuit. Electricity Supply. (d) where the supply is for any special purpose other than those above mentioned, or where the pressure of the supply exceeds the limits of medium pressure, it shall be subject to such other regulations as the Governor in Council may prescribe. 3. When the pressure between the outer conductors of a three-wire system exceeds 250 volts and the three wires of the system or two pairs of wires are brought into a consumer's premises, the supply shall be given to two pairs of terminals arranged in such a manner that there shall be no danger of any shock, and the wiring from those terminals shall be kept distinct. 4. The sectional area of the conductor in any electric line other than low tension laid or erected in any street after 2nd December, 1921, shall not be less than that of a strand of seven wires, each of which is of No. 22 standard wire gauge, and the sectional area of every wire in a strand forming any such conductor shall not be less than that gauge, and where such stranded conductor is erected it shall be suspended from a suitable bearer wire or shall be protected by a suitable cradle fixed underneath. In the case of low tension conductors in any electric line the sectional area shall not be less than that of a single wire of No. 16 standard wire gauge efficiently insulated. This regulation shall not apply in the case of an electric line placed in a lamp post. 5. Every low pressure and medium pressure main, after having been placed in position and before it is used for the purposes of supply, shall withstand a pressure equal to the maximum pressure to which it is intended to be subjected in use, and in any case at least 200 volts, and further, before being used as aforesaid it shall be tested for insulation, and the company shall duly record the results of the tests of each main or section of a main. 6. A high pressure circuit shall not be brought into use unless the insulation of every part thereof has withstood the continuous application, during one hour, in the case of every electric line, of a pressure equal to the full 180
Baseline (Original)
CAP. 103] [г. 2 cont.] Introduction of three-wire system into consumer's premises. Minimum size of conductors. Insulation test of low pressure and medium pressure mains. Testing of insulation of all parts of high pressure circuit. Electricity Supply. (d) where the supply is for any special purpose other than those above mentioned, or where the pressure of the supply exceeds the limits of medium pressure, it shall be subject to such other regula- tions as the Governor in Council may prescribe. 3. When the pressure between the outer conductors of a three-wire system exceeds 250 volts and the three wires of the system or two pairs of wires are brought into a consumer's premises, the supply shall be given to two pairs of terminals arranged in such a manner that there shall be no danger of any shock, and the wiring from those terminals shall be kept distinct. 4. The sectional area of the conductor in any electric line other than low tension laid or erected in any street after 2nd December, 1921, shall not be less than that of a strand of seven wires, each of which is of No. 22 standard wire gauge, and the sectional area of every wire in a strand forming any such conductor shall not be less than that gauge, and where such stranded conductor is erected it shall be suspended from a suitable bearer wire or shall be protected by a suitable cradle fixed underneath. In the case of low tension conductors in any electric line the sec- tional area shall not be less than that of a single wire of No. 16 standard wire gauge efficiently insulated. This regulation shall not apply in the case of an electric line placed in a lamp post. 5. Every low pressure and medium pressure main, after having been placed in position and before it is used for the purposes of supply, shall withstand a pressure equal to the maximum pressure to which it is intended to be subjected in use, and in any case at least 200 volts, and further, before being used as aforesaid it shall be tested for insulation, and the company shall duly record the results of the tests of each main or section of a main. 6. A high pressure circuit shall not be brought into use unless the insulation of every part thereof has with- stood the continuous application, during one hour, in the case of every electric line, of a pressure equal to the full 180 !
2026-05-03 20:34:43 · Baseline
View content

CAP. 103]

[г. 2 cont.]

Introduction of three-wire system into consumer's premises.

Minimum size of conductors.

Insulation test of low pressure

and medium pressure mains.

Testing of insulation

of all parts of high

pressure circuit.

Electricity Supply.

(d) where the supply is for any special purpose other than those above mentioned, or where the pressure of the supply exceeds the limits of medium pressure, it shall be subject to such other regula- tions as the Governor in Council may prescribe.

3.

When the pressure between the outer conductors of a three-wire system exceeds 250 volts and the three wires of the system or two pairs of wires are brought into a consumer's premises, the supply shall be given to two pairs of terminals arranged in such a manner that there shall be no danger of any shock, and the wiring from those terminals shall be kept distinct.

4. The sectional area of the conductor in any electric line other than low tension laid or erected in any street after 2nd December, 1921, shall not be less than that of a strand of seven wires, each of which is of No. 22 standard wire gauge, and the sectional area of every wire in a strand forming any such conductor shall not be less than that gauge, and where such stranded conductor is erected it shall be suspended from a suitable bearer wire or shall be protected by a suitable cradle fixed underneath. In the case of low tension conductors in any electric line the sec- tional area shall not be less than that of a single wire of No. 16 standard wire gauge efficiently insulated.

This regulation shall not apply in the case of an electric line placed in a lamp post.

5. Every low pressure and medium pressure main, after having been placed in position and before it is used for the purposes of supply, shall withstand a pressure equal to the maximum pressure to which it is intended to be subjected in use, and in any case at least 200 volts, and further, before being used as aforesaid it shall be tested for insulation, and the company shall duly record the results of the tests of each main or section of a main.

6.

A high pressure circuit shall not be brought into use unless the insulation of every part thereof has with- stood the continuous application, during one hour, in the case of every electric line, of a pressure equal to the full

180

!