Appeal to Director of Public Works.
Penalty of
addition to
222
any consumer's premises, by notice require the consumer at some reasonable time after the service of the notice to permit him to inspect and test the wires and fittings belonging to the consumer and forming part of the circuit.
If on any such testing the officer discovers an undue leakage from the consumer's wires or if the consumer does not give all due facilities for inspection and testing, the company shall forthwith discontinue the supply of energy to the premises in question, giving immediate notice of the discontinuance to the consumer, and shall not recommence the supply until they are reasonably satisfied that the leakage has been removed.
32. If any consumer is dissatisfied with the action of the company in refusing to give, or in discontinuing or in not recommencing the supply of energy to his pre- mises, the wires and fittings of that consumer shall, on his application and on payment of a fee of ten dollars, be tested for the existence of leakage by the Director of Public Works.
This regulation shall be endorsed on every notice given under the provisions of either of the two last pre- coding regulations.
33. Any consumer making any addition to the elec- consumer for trical installation on his premises without giving due notice to the company to enable them to test the same before connecting it to the existing installation shall be liable to a penalty not exceeding fifty dollars for every such addition.
electrical
installation
without
notice to
company.
Height from ground.
Are lamps to be
guarded.
Connection with earth
of a three-
Are Lighting.
34. Arc lamps used in any street for public lighting shall be so fixed as not to be in any part at a less height than 10 feet from the ground.
35. All are lamps shall be so guarded as to prevent pieces of ignited carbon or broken glass falling from them, and shall not be used in situations where there is any danger of the presence of explosive dust or gas.
Connection of Circuits with Earth.
36. Where the pressure of a supply between the ad- jacent conductors of a three-wire system of mains exceeds 125 volts, the intermediate conductor shall be wire system. connected with earth in accordance with the following
conditions:-
Connection
(a.) The connection with earth of the intermediate conductor shall be made at one point only
oll
the
trans-
each distinct circuit, namely, at generating station, sub-station, or former, and the insulation of the circuit shall be efficiently maintained at all other parts. (L.) The current from the intermediate conductor to earth shall be continuously recorded, and, if it at any time becomes excessive, steps shall be immediately taken to improve the insulation of the systom.
37. The company shall not connect any other circuit with earth except with the approval of the Director of circuits with Public Works and subject to such conditions as he may
of other
carth.
Special regulations
as to extra high pressure.
prescribe.
Extra High Pressure.
38.-(1.) This regulation shall have effect in the case of a supply at extra high pressure and shall be in addition to and not in substitution for the obligations imposed by the foregoing regulations.
(2.) An extra high pressure main shall not be brought into use unless, after it has been placed in position and before it is used for the purposes of supply, the insula- tion of every part thereof has withstood the continuous application, during half-an-hour, of pressure exceeding the maximum pressure to which it is intended to be sub- jected in use, that is to say, in the case of every electric line to be used for a pressure not exceeding 10,000